| Keterangan: | Panel
— — Panel size : 600 x 600 mm ± 0, 2 mm
— — Nominal thickness 30 ± 0, 3 mm
— — Squareness diagonally ± 0, 3 mm
— — Composition Fibre reinforced calsium sulphate, with 0, 5 mm
galvanized steel sheet, edgebanded on 4 edges
— — Coverings HPL, vinyls and various other kinds. Covering
must be selected to meet mechanical and
electrical demands. A wide range even for
exeptional requirements is avaliable.
Weights
— — Per panel Approximately 18 kg
— — Per sqm Approximately 50 kg
Technical data
— — Distributed load N/ m2 30.000
— — Concentrated load N 5.500
— — Max. discharge resistance/ ohm
( depending on covering) Approx. 106
— — Thermal conductivity W/ mk 0, 58
— — Floor normalised level
difference dB 54
— — Fire rating DIN 4102 minutes 60
Material classification
— — DIN 4102 A ( incombustable)
— — BS476 part 7 class 1
— — ASTM E-84-81 a
Flame spread index : 0
— — Smoke developed value : 10
— — Height of floor void
between concrete floor
and panel FFL minus 32 mm
— — Possible Finished Floor
Level ( FFL) mm 77-1000*
* higher FFL with reinforced subcostruction
Various Accesories
— — Electrical outlets, stairs, ramps, panel lifting devices, air and
fire barriers, skirtings, bulkheads ventilation panels etc.
Non-combustible materials constantly provide the greatest
realibility with regard to fire protection. In addition to this,
Lindner in-house production means that we can even control
the raw materials used. the panels are recommended by the
Institube for Contruction Biology in Rosenheim, Germany.
Additionaly, emission test carried out show that the product is
ideal for use in almost any type of environment. |